SUBCODE "PM" (THE PHILADELPHIA PROPERTY MAINTENANCE CODE)
SECTION PM-605.0 FIRE PROTECTION SYSTEMS
PM-605.1 General: All systems, devices and equipment to detect
a fire, actuate an alarm, or suppress or control a fire or any combination
thereof shall be properly maintained.
PM-605.2 Fire suppression
system: Fire suppression systems shall be in proper operating condition at
all times.
PM-605.2.1 Valves: Control valves shall be in the
fully open position.
PM-605.2.2 Sprinklers: Sprinklers shall be
clean and free of corrosion, paint and damage. Stock shall be at least 18 inches
(457 mm) below sprinkler deflectors.
PM-605.2.3 Piping: Piping
shall be properly supported and shall not support any other
loads.
PM-605.3 Standpipe systems: Standpipe systems shall be in
proper operating conditions at all times.
PM-605.3.1 Valves:
Water supply control valves shall be in the fully open
position.
PM-605.3.2 Hose connections: Hose connections shall
be identified and have ready access thereto.
PM-605.3.3 Hose:
Where provided, the hose shall be properly packed, dry and free from
deterioration.
PM-605.4 Fire alarm systems: Fire alarm systems shall be in proper
operating condition at all times.
PM-605.4.1 Control panel: The "power on" indicator shall be lit.
Alarm or trouble indicators shall not be illuminated.
PM-605.4.2
Manual fire alarm boxes: All manual fire alarm boxes shall be operational
and unobstructed.
PM-605.4.3 Automatic fire detectors: All
automatic fire detectors shall be operational and free from any obstructions
that prevent proper operation, including smoke entry.