SUBCODE "PM" (THE PHILADELPHIA PROPERTY MAINTENANCE CODE)
SECTION PM-503.0 VENTILATION
PM-503.1 Bathrooms and toilet rooms: Every bathroom and toilet
room shall be equipped with natural or mechanical ventilation in accordance with
Sections PM-503.1.1 or PM-503.1.2.
PM-503.1.1 Natural ventilation:
Natural ventilation shall be provided by openable area equal to or greater
than 4 percent of the bathroom or toilet room served.
PM-503.1.2
Mechanical ventilation: Air exhausted by a mechanical ventilation system
from all bathrooms or toilet rooms shall comply with the mechanical code or
shall provide a minimum of 6 air changes per hour to the space and shall be
exhausted to the exterior without recirculation to any space, or not more than
85 percent of the exhaust air shall be recirculated where the system is provided
with effective absorption and filtering equipment.
PM-503.2 Process
Ventilation: Where injurious, toxic, irritating or noxious fumes, gases,
dusts or mists are generated, a local exhaust ventilation system shall be
provided to remove the contaminating agent at the source. Air shall be exhausted
to the exterior in accordance with The Philadelphia Code and not be recirculated
to any space.