SUBCODE "PM" (THE PHILADELPHIA PROPERTY MAINTENANCE CODE)
SECTION PM-403.0 VENTILATION
PM-403.1 Habitable spaces: Every habitable space except
kitchens shall have at least one openable window or skylight. The total openable
area of the window in every room shall be equal to at least 45 percent of the
minimum glazed area required in Section PM-402.1.3 and 402.1.4. A window which
is disqualified by Section PM-402.1.1 or PM-402.1.2 shall also be disqualified
as openable area.
Exception: Mechanical ventilation which complies
with the mechanical code or which provides six air changes per hour to the space
and exhausts to the outside shall be accepted in lieu of openable
windows.
PM-403.2 Bathrooms and toilet rooms: Every bathroom and
toilet room shall comply with the ventilation requirements for habitable spaces
as required by Section PM-403.1, except that a window or skylight shall not be
required in spaces equipped with a mechanical ventilation system which exhausts
air from a toilet room or bathroom within a dwelling or rooming unit to the
exterior without recirculation to any space, including the space from which such
air is withdrawn.
PM-403.3 Laundry rooms: Every laundry room
shall have a minimum openable area of two square feet (0.19
m2).
Exception: Mechanical ventilation which provides
six air changes per hour to the room and exhausts to the outside shall be
accepted in lieu of the openable area.
PM-403.4 Clothes dryers:
Clothes dryer venting systems shall be independent of all other systems and
shall be vented in accordance with the manufacturer’s
instructions.