PM-402.1 Habitable spaces: Every habitable space except
kitchens shall have at least one window or skylight of approved size facing
directly to the outdoors.
PM-402.1.1 Obstructions: Wherever
walls or other portions of a structure face a window of any room and such
obstructions are located less than 3 feet (914 mm) from the window and extend to
a level above that of the ceiling of the room, such window shall not be deemed
to face directly to the outdoors and shall not be included as contributing to
the required minimum total window area for the room.
PM-402.1.2
Basement habitable spaces: The required window area serving habitable spaces
in basements shall have a minimum outside horizontal clear space measured
perpendicular to the window, equal to one and one-half times the depth of the
window sill below average adjoining grade.
PM-402.1.3 Window area:
The minimum total window area of every sleeping room with 100 square feet
(9.29 m
2) or less of floor area shall be eight percent of the floor
area. The minimum total window of every sleeping room with more than 100 square
feet (9.29 m
2) of floor area shall be eight square feet plus five
percent of each square foot of floor area over 100 square feet (9.29
m
2). The minimum total window area of every other habitable room for
which windows are required shall be seven percent of the floor
area.
PM-402.1.4 Adjoining spaces: Where natural light for
rooms or spaces without exterior window areas is provided through an adjoining
room or enclosed porch, the unobstructed opening to the adjoining room shall be
at least eight percent of the floor area of the interior room or space, but not
less than twenty-five square feet (2.33 m
2). The exterior window area
shall be based on the total floor area being served.
PM-402.2 Common
halls and stairways:[73.1]
Every common hall, interior stairway and exterior stairway serving
residential occupancies shall be provided with artificial light capable of
providing a minimum of one footcandle (11 lux) at floors, landings and treads.
Continuous operation of the lighting system is required except during those
hours when there is sufficient natural light to comply with these
requirements.
Exception: Continuous operation is not required for
common hall and stairway lighting serving occupancies in Group R-3 which are
equipped with light switches located within three feet (914 mm) of the access
and entrance doors to such common spaces.
PM-402.3 Other spaces:
All other spaces shall be provided with natural or artificial light
sufficient to permit the maintenance of sanitary conditions, and the safe
occupancy of the space and utilization of the appliances, equipment and
fixtures.