SUBCODE "F" (THE PHILADELPHIA FIRE CODE)
SECTION F-914 PERIODIC TESTING OF FIRE PROTECTION SYSTEMS
F-914.1 Periodic test frequency. Fire
protection systems, including standby/emergency generators in all buildings and
all standby and emergency electrical systems in high-rise buildings shall be
tested annually. The owner of each building that contains emergency electrical
systems, automatic fire extinguishing systems, standpipe systems or fire alarm
systems shall annually provide a certification for such systems in the building
from a person certified or licensed by the Department of Licenses and
Inspections to provide such certifications in accordance with regulations
promulgated pursuant to this
code.
Exceptions:
1. An owner is not
required to submit certification of smoke alarms in one- and two-family
dwellings or single- and multiple-station smoke alarms (non-system smoke
detectors) in other occupancies.
2. An owner is not required to
submit certification of tests, inspections and maintenance of fire protection
equipment recommended by equipment manufacturers or referenced standards to be
performed at times more frequently than annually.
F-914.1.1
Submission of certification. The certification shall indicate that the fire
protection system has been tested and maintained in accordance with the
requirements of this chapter and the applicable NFPA standards. The
certification or a notice of deficiencies that preclude certification of the
system shall be submitted in approved form to the Department of Licenses and
Inspections.
F-914.1.2 Seal. Paper
forms of certifications submitted to the City of Philadelphia, to the owner, or
for any other official purpose shall be embossed with the impression seal of the
company that performed the certification.
F-914.1.3
Intent. The requirement for annual certification is to confirm
the proper function of the system(s) previously installed in a building in
accordance with the provisions of the referenced codes and standards applicable
to existing buildings. This requirement shall not be construed as requiring
existing systems to comply with the provisions of codes and standards applicable
to new buildings or new systems.
F-914.1.4
Partial certification. When a fire suppression system is
repaired, altered or extended between periodic testing dates, the modified
portion of the system is required to be certified upon a return to service. When
the entire system is certified upon return to service at the owner’s
discretion, the date of certification will become the new periodic test
date.
F-914.1.5 Annual certification of fire
suppression system during period of retrofit or new installation.
During the period of sprinkler and/or standpipe retrofit or new installation,
the normal certification procedures shall continue to apply to existing systems
and to completed portions of new installations.
F-914.2
Consistency of required test dates. To ensure consistency of
required tests for sprinkler and standpipe systems, tests shall be conducted in
accordance with the dates indicated in Sections F-914.2.1 through
F-914.2.4
F-914.2.1 Dry pipe
valves. Full flow tests of dry pipe valves shall be required in 1996
and every three years thereafter, except those protecting areas that are
constantly maintained below a freezing
temperature.
F-914.2.2 Standpipe pressure
reducing valves. Flow tests of standpipe pressure reducing valves
shall be required in 1995 and every five years
thereafter.
F-914.2.3 Dry standpipe system
hydrostatic test. Hydrostatic tests of dry standpipe systems and dry
portions of wet standpipe systems shall be required in 1995 and every five years
thereafter.
F-914.2.4 Standpipe flow
test. Standpipe flow tests conducted at the hydraulically most remote
hose connection shall be required in 2005 and every five years
thereafter.
F-914.3 Annual audibility testing
in Groups I-1, R-1, R-2 and R-4. In Group I-1, R-1, R-2 and R-4
occupancies, the annual certification of the fire alarm systems shall contain
the results of audibility tests performed in accordance with NFPA 72 in the
sleeping rooms of a representative sample of units contained within the
building. The specific units tested and the audibility readings taken shall be
entered on the annual certification form. The sample shall include as a
minimum:
1. One of each type of unit contained in the building;
and
2. The unit or units that are most remote from the audible
alarm notification appliances; and
3. Any unit or units with
sleeping rooms that are separated from the corridor by building cores, such as
elevator cores, stairways, etc; and
4. One unit per
floor.