SECTION F-106 MAINTENANCE


F-106.1 Maintenance of safeguards. Where any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards.

F-106.2 Testing and operation. Equipment requiring periodic testing or operation to ensure maintenance shall be tested or operated as specified in this code.

F-106.2.1 Test and inspection records. Required test and inspection records shall be available to the fire code official at all times or such records as the fire code official or this code designates, shall be filed with the fire code official.

F-106.2.2 Reinspection and testing. Where any work or installation does not pass an initial test or inspection, the necessary corrections shall be made so as to achieve compliance with this code. The work or installation shall then be reinspected or re-tested and the results resubmitted to the fire code official as appropriate.

F-106.3 Supervision. Maintenance and testing shall be under the supervision of a responsible person who shall ensure that such maintenance and testing are conducted at specified intervals in accordance with this code.

F-106.4 Rendering equipment inoperable. Portable or fixed fire-extinguishing systems or devices and fire-warning systems shall not be rendered inoperative or inaccessible except as necessary during emergencies, maintenance, repairs, alterations, drills or prescribed testing. The restoration of protection shall be diligently pursued.

F-106.4.1 Fire Department notification. The Fire Department shall be notified by telephone at 215-922-6000 of the shutdown of any fire protection system that affects more than one story or more than 30,000 square feet on one story. This notification shall occur immediately upon knowledge of an unplanned loss of protection and prior to the interruption of protection in the case of tests, maintenance, repairs, alterations or additions. The notification shall include the extent of and reason for such interruption of protection and the anticipated length of outage. The Fire Department shall be notified again immediately upon restoration of service.

F-106.5 Owner/occupant responsibility. Correction and abatement of violations of this code shall be the responsibility of the owner. If an occupant creates, or allows to be created, hazardous conditions in violation of this code, the occupant shall also be held responsible for the abatement of such hazardous conditions.

F-106.6 Overcrowding. Overcrowding or admittance of any person beyond the lawful occupancy of a building or a portion thereof constitutes a violation of this code. Upon finding any overcrowding or unlawful occupancy, the fire code official, in addition to any other remedy under this code, is authorized to cause any event or activity to be stopped until such overcrowding or unlawful occupancy is corrected.

F-106.7 Obstructions. An obstruction in an aisle, passageway or other means of egress constitutes a violation of this code. Upon finding any obstruction in an aisle, passageway or other means of egress, or upon finding any condition that constitutes a life safety hazard, the fire code official, in addition to any other remedy under this code, is authorized to cause any event or activity to be stopped until such condition or obstruction is corrected.