SUBCODE "F" (THE PHILADELPHIA FIRE CODE)
SECTION F-106 MAINTENANCE
F-106.1 Maintenance of safeguards. Where any device,
equipment, system, condition, arrangement, level of protection, or any other
feature is required for compliance with the provisions of this code, or
otherwise installed, such device, equipment, system, condition, arrangement,
level of protection, or other feature shall thereafter be continuously
maintained in accordance with this code and applicable referenced
standards.
F-106.2 Testing and operation.
Equipment requiring periodic testing or operation to ensure maintenance shall be
tested or operated as specified in this code.
F-106.2.1 Test
and inspection records. Required test and inspection records shall be
available to the fire code official at all times or such records as the fire
code official or this code designates, shall be filed with the fire code
official.
F-106.2.2 Reinspection and testing. Where any
work or installation does not pass an initial test or inspection, the necessary
corrections shall be made so as to achieve compliance with this code. The work
or installation shall then be reinspected or re-tested and the results
resubmitted to the fire code official as appropriate.
F-106.3
Supervision. Maintenance and testing shall be under the supervision
of a responsible person who shall ensure that such maintenance and testing are
conducted at specified intervals in accordance with this
code.
F-106.4 Rendering equipment inoperable.
Portable or fixed fire-extinguishing systems or devices and fire-warning systems
shall not be rendered inoperative or inaccessible except as necessary during
emergencies, maintenance, repairs, alterations, drills or prescribed testing.
The restoration of protection shall be diligently
pursued.
F-106.4.1 Fire Department notification. The
Fire Department shall be notified by telephone at 215-922-6000 of the shutdown
of any fire protection system that affects more than one story or more than
30,000 square feet on one story. This notification shall occur immediately upon
knowledge of an unplanned loss of protection and prior to the interruption of
protection in the case of tests, maintenance, repairs, alterations or additions.
The notification shall include the extent of and reason for such interruption of
protection and the anticipated length of outage. The Fire Department shall be
notified again immediately upon restoration of service.
F-106.5
Owner/occupant responsibility. Correction and abatement of violations
of this code shall be the responsibility of the owner. If an occupant creates,
or allows to be created, hazardous conditions in violation of this code, the
occupant shall also be held responsible for the abatement of such hazardous
conditions.
F-106.6 Overcrowding. Overcrowding or
admittance of any person beyond the lawful occupancy of a building or a portion
thereof constitutes a violation of this code. Upon finding any overcrowding or
unlawful occupancy, the fire code official, in addition to any other remedy
under this code, is authorized to cause any event or activity to be stopped
until such overcrowding or unlawful occupancy is
corrected.
F-106.7 Obstructions. An obstruction in
an aisle, passageway or other means of egress constitutes a violation of this
code. Upon finding any obstruction in an aisle, passageway or other means of
egress, or upon finding any condition that constitutes a life safety hazard, the
fire code official, in addition to any other remedy under this code, is
authorized to cause any event or activity to be stopped until such condition or
obstruction is corrected.