SUBCODE "F" (THE PHILADELPHIA FIRE CODE)
CHAPTER 9 FIRE PROTECTION SYSTEMS
F-901.4.5 Tagging of equipment. A tag shall be attached to
each fire alarm system, automatic fire extinguishing system and standpipe system
that is installed, repaired or serviced. The tag shall indicate the date of the
work and the name, address and telephone number of the person or company that
performed the work.
F-901.4.6 Changes to fire protection
equipment. Where there is a change to any fire protection or emergency
electrical equipment or other building systems that are available for use during
fire department operations in a building, the Fire Department shall be notified
immediately. Detailed information and instructions for all equipment changes
shall be provided to the Fire Department.
F-901.5 Installation acceptance testing. Fire detection and alarm
systems, fire-extinguishing systems, fire hydrant systems, fire standpipe
systems, fire pump systems, private fire service mains and all other fire
protection systems and appurtenances thereto shall be subject to acceptance
tests as contained in the installation standards and as approved by the fire
code official. The fire code official shall be notified before any required
acceptance testing. Test results shall be submitted to the Department of
Licenses and Inspections in approved form.
F-901.5.2 Test requirements. The acceptance tests required by
this chapter shall be conducted by a person certified or licensed by the
Department of Licenses and Inspections for the specific systems in accordance
with regulations issued pursuant to this code. Tests required by this code and
the referenced standards shall be conducted at the expense of the owner or the
owner’s representative.
F-901.6 Inspection, testing and
maintenance. Fire detection, alarm and extinguishing systems shall be
maintained in an operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems and equipment
shall be inspected, tested and maintained or shall be removed upon
obtaining the required permit from the Department of Licenses and
Inspections.
F-901.6.2 Records. Records of all system inspections,
tests, and maintenance required by the referenced standards shall be maintained
on the premises for a minimum of 3 years and made available to the fire code
official upon request.
Exception: The written log of tests
shall not be required in occupancies in Use Group
R-3.
F-901.6.3 Test responsibility and notification. The
fire code official shall not be held responsible for any damages incurred during
any test required under the provisions of this chapter. When the fire code
official requests to be present for a test, the fire code official shall be
notified not less than 48 hours before said test is conducted.
F-901.7 Systems out of service. Where a required fire protection
system is out of service, the fire department [and the fire code
official] shall be notified immediately in accordance with, and under
conditions specified in, Section F-106.4.1. [and,
w]Where required by the fire code official, the building shall
either be evacuated or an approved fire watch shall be provided for all
occupants left unprotected by the shut down until the fire protection system has
been returned to service.
Where utilized, fire watches shall be provided
with at least one approved means for notification of the fire department and
their only duty shall be to perform constant patrols of the protected premises
and keep watch for fires. In the event that the fire watch observes smoke or
fire, the fire department shall be notified immediately. The fire department
shall be notified upon the return of the system to service.
F-901.7.7 Vacant buildings. Fire alarm systems in vacant
buildings are not required to remain in service. Sprinkler systems and automatic
water supplies for wet standpipe systems in vacant buildings are not required to
remain in service where the Fire Department determines it is safe to discontinue
the protection and provides written approval.
F-901.9 Certification and licensing. No person shall
install, alter, repair, service or test fire alarm systems, automatic fire
extinguishing systems or standpipe systems unless that person is certified or
licensed as required by the Philadelphia Administrative Code, this code and the
regulations issued pursuant thereto.
F-901.10 Notification to
fire department of fire alarm. The Fire Department shall be notified
immediately by the owner, tenant or occupant of any building and by a central
station service of the activation of any fire alarm signal initiated by manual
fire alarm boxes, automatic fire detectors, waterflow alarms from automatic fire
extinguishing systems, and any other fire protection equipment.
F-903.3.7 Fire department connections. [The location of fire]
Fire department connections shall be [approved by the fire code
official] located in accordance with Section F-912.
F-903.6 Existing buildings. The provisions of this section are
intended to provide a reasonable degree of safety in existing structures not
complying with the minimum requirements of the building code by requiring
installation of an automatic fire-extinguishing system in accordance with
this section and Section F-903.3. Systems shall be monitored in accordance with
Section F-903.6.7. Except where inappropriate for the hazard, fire
extinguishing systems that are newly installed to comply with this section shall
be automatic sprinkler systems installed in accordance with this code and NFPA
13, NFPA 13R or NFPA 13D.
F-903.6.2 Basements without openings. Basements exceeding 2500
square feet (232 m2) without openings that conform to the provisions
of Section F-903.2.10.1 and its subsections shall be equipped with an approved
automatic fire extinguishing
system.
Exceptions:
1. Basements containing
no occupancy or storage, excluding permanently installed building service
equipment, but not excluding oil cooled electrical
equipment.
2. Group R-3 and Group U
occupancies.
F-903.6.3 High-hazard occupancies. An
automatic fire extinguishing system shall be installed throughout high-hazard
occupancies.
F-903.6.4 High-rise buildings. An automatic
fire extinguishing system shall be installed throughout high-rise
buildings.
Exception. Portions of high-rise buildings
currently occupied by Group R-2 occupancies without change in use since December
18, 1991.
F-903.6.5 High-rise Group R-2 occupancies. An
automatic fire extinguishing system shall be installed in the following areas of
Group R-2 occupancies in the portions of high-rise buildings to which the
requirements of Subsection F-903.6.4 do not apply.
1. Basements
in accordance with Section F-903.6.2.
2. Rooms used for the
storage of combustibles where the floor area exceeds 120 square feet (11
m2).
3. Trash and incinerator chutes and
rooms.
Exception to #3: In buildings where an automatic
fire extinguishing system is not required throughout the building and where the
trash chute access room or compartment is completely enclosed by fire barriers
having a fire resistance rating of not less than one hour and is not used for
the temporary or permanent storage of combustible materials, the automatic fire
extinguishing system is not required in the access room or
compartment.
F-903.6.6 Group I-4 child care facilities.
An automatic fire-extinguishing system shall be installed throughout all Group
I-4 child care facilities.
Exceptions: Group I-4 child
care facilities legally in existence prior to January 1, 1984 where all children
less than 2½ years of age are kept on the level of exit
discharge.
F-903.6.7 Monitoring of existing fire
extinguishing systems. Automatic fire extinguishing systems installed on or
after March 1, 1991 and automatic sprinkler systems installed in Group H and I
occupancies and high-rise buildings prior to March 1, 1991, shall be monitored
in accordance with Sections F-903.4 and F-904.3.5 as applicable. Where systems
are monitored on site at a constantly attended location, approval of the fire
code official is not required.
F-905.1 General. Standpipe systems shall be provided in new and
existing buildings and structures in accordance with this section.
[Fire hose threads used in connection with standpipe systems shall be
approved and shall be compatible with fire department hose threads. The location
of fire department hose connections shall be approved.] Fire
department connections shall be installed in accordance with Section F-912.
In buildings used for high-piled combustible storage, fire protection shall be
in accordance with Chapter 23.
F-905.2 Installation standards.
Standpipe systems shall be installed in accordance with this section and NFPA
14.
F-905.2.1 Pressure regulating devices. Pressure
regulating devices shall be used on new and existing standpipe systems as
specified in Sections F-905.2.1.1 through
F-905.2.1.3.
F-905.2.1.1 Class I and Class III wet
standpipes. Where, and only where, static or residual water pressures at any
Class I or Class III fire department use standpipe hose outlet exceed 175 psi
(1207 kPa), approved pressure-regulating devices shall be installed to limit the
pressure to 175 psi (1207 kPa). Such devices shall regulate pressure under flow
and no-flow conditions and shall be adjusted to provide 175 psi (1207 kPa), or
as close to that pressure as the adjustment will permit, without exceeding 175
psi (1207 kPa). The pressure on the inlet side of the pressure-regulating device
shall not exceed the rated working pressure of the
device.
F-905.2.1.2 Class I dry standpipes. No pressure
regulating device shall be installed on any dry standpipe system having no
permanent water supply.
F-905.2.1.3 Class II and Class III
standpipes. Where residual water pressure at any Class II or Class III
building occupant use standpipe hose outlet exceeds 100 psi (690 kPa), approved
pressure-regulating devices shall be installed to limit the pressure to 100 psi
(690 kPa).
F-905.3.1 Building height. Class III automatic wet
standpipe systems shall be installed throughout buildings where the floor level
of the highest story is located more than 30 feet (9144 mm) above the lowest
level of the fire department vehicle access, or where the floor level of the
lowest story is located more than 30 feet (9144 mm) below the highest level of
fire department vehicle
access.
Exceptions:
1. Class I standpipes are
allowed in buildings equipped throughout with an automatic sprinkler system in
accordance with Section F-903.3.1.1 or F-903.3.1.2.
2. Class I manual
standpipes are allowed in open parking garages where the highest floor is
located not more than 150 feet (45 720 mm) above the lowest level of fire
department vehicle access.
3. [Class I manual dry standpipes are
allowed in open parking garages that are subject to freezing temperatures,
provided that the hose connections are located as required for Class II
standpipes in accordance with Section F-905.5.
4. ]Class I standpipes are allowed in basements equipped throughout
with an automatic sprinkler system.
F-905.4 Location of Class I standpipe hose connections. Class I
standpipe hose connections shall have 2½ inch (64 mm) male
National Hose standard threads and shall be provided in all of the following
locations:
1. In every required stairway, a hose connection shall be
provided for each floor level above or below grade. Hose connections shall be
located at an intermediate floor level landing between floors, unless otherwise
approved by the [fire code official]
Department.
Where a building contains stairways in addition to
the required exit stairways, the additional stairways are subject to this
section where they meet the criteria for exit stairways, including the exit
discharge criteria. Where an additional stairway discharges in accordance with
Section F-1023.1, it is subject to the provisions of this section.
F-905.8 Dry standpipe. Dry standpipes shall not be
installed.
Exceptions:
1. Where subject to
freezing, automatic dry and semiautomatic dry standpipe systems are
permitted [and] in accordance with NFPA
14.
2. Where otherwise permitted by Section
F-905.
F-905.11 Existing buildings. Existing structures with occupied
floors located more than 50 feet (15,240 mm) above or below the lowest level of
fire department vehicle access shall be equipped with standpipes
installed in accordance with Section F-905. The standpipes shall have an
approved fire department connection with hose connections at each floor level
above or below the lowest level of fire department vehicle access.
[The fire code official is authorized to approve the installation of
manual standpipe systems to achieve compliance with this section where the
responding fire department is capable of providing the required fire flow at the
highest standpipe outlet.] These requirements shall also apply to
buildings that were granted variances prior to January 1, 2004 to omit
standpipes from the required exit stairways. Buildings or structures that
are not in compliance with Section F-905 on the effective date of this
code, shall, with written request to and upon written approval from the Fire
Department, be granted three years from the effective date of this code to
comply.
Exceptions:
1. In existing
buildings having the highest occupied floors located not more than 75 feet above
the lowest level of fire department vehicle access, Class I standpipe systems
are permitted to be manual wet systems.
2. Standpipe systems
installed prior to January 1, 1995 that provide a residual pressure of 65 psi
(448 kPa) or greater at the highest hose outlet are exempt from the requirement
to provide a residual pressure of 100 psi (690 kPa) at the highest hose
outlet.
3. Standpipe systems with a residual pressure of less
than 100 psi (690 kPa) at the topmost hose outlet are permitted
where:
3.1 The building existing prior to the effective date
of this code;
3.2 The building is equipped throughout with an
automatic sprinkler system; and
3.3 The highest floor level is
not more than 150 feet (45 720 mm) above the lowest level of fire department
vehicle access,
F-905.11.1 Removal of occupant use hoseline
or Class II standpipe systems. Removal of the hoseline attached to a Class
II standpipe system or a Class III standpipe system that is not required by this
code, or removal of an entire Class II standpipe system is permitted where the
following conditions are met:
1. Removal of hoseline only: The
building is equipped with a Class I standpipe system or the building is not
required to have a Class I system.
2. Removal of the Class II
standpipe system is permitted where one of the following
exists:
2.1 The building is equipped throughout with an
automatic fire-extinguishing system and has more than one Class I standpipe hose
outlet riser in a multi-exit building or at least one riser in a single exit
building;
2.2 The building is in the process of being equipped
throughout with an automatic fire-extinguishing system and there is more than
one standpipe hose outlet riser in a multi-exit building or there is at least
one riser in a single exit building. When the sprinklers on a floor have been
placed in service, the Class II standpipe hose stations on that floor are
permitted to be removed; or
2.3 The building is not equipped
throughout with an automatic fire-extinguishing system, there is more than one
automatic wet Class I standpipe hose outlet riser in a multi-exit building and
there is at least one automatic wet riser in a single exit
building.
F-906.2 General requirements. Fire extinguishers shall be
selected, installed and maintained in accordance with this section and NFPA 10.
A tag shall be attached to each fire extinguisher indicating inspections and
maintenance performed during the past 12
months.
Exceptions:
1. In Group R-2
occupancies one fire extinguisher with a minimum rating of 2-A:10-B:C mounted in
each dwelling unit shall be permitted in lieu of mounting them in the common or
public corridors or stairways.
2. The travel distance to reach an extinguisher shall not apply to
the spectator seating portions of Group A-5 occupancies.
F-907.1.2 Equipment. Systems and their components shall be
listed and approved for the purpose for which they are installed.
Installation of systems, devices, appliances and equipment shall be in
accordance with the provisions of Section F-907 and NFPA
72.
F-907.2 Where required -- new buildings and structures.
An approved manual, automatic, or manual and automatic fire alarm system shall
be provided in new buildings and structures in accordance with Sections
F-907.2.1 through F-907.2.[23]24. Where automatic sprinkler
protection installed in accordance with Section F-903.3.1.1 or F-903.3.1.2 is
provided and connected to the building fire alarm system, automatic heat
detection required by this section shall not be required.
An approved
automatic fire detection system shall be installed in accordance with the
provisions of this code and NFPA 72. Devices, combinations of devices,
appliances and equipment shall comply with Section F-907.1.2. The automatic fire
detectors shall be smoke detectors, except that an approved alternative type of
detector shall be installed in spaces such as boiler rooms where, during normal
operation, products of combustion are present in sufficient quantity to actuate
a smoke detector.
F-907.2.1 Group A. A manual fire alarm system shall be
installed in accordance with NFPA 72 in Group A occupancies having an occupant
load of 300 or more and in all Special Assembly Occupancies. Portions of
Group E occupancies occupied for assembly purposes shall be provided with a fire
alarm system as required for the Group E
occupancy.
Exceptions:
1. Manual
fire alarm boxes are not required where the building is equipped throughout with
an automatic sprinkler system and the alarm notification appliances will
activate upon sprinkler water flow.
2. Manual fire alarm boxes are
not required in Special Assembly Occupancies where the occupancy is protected
throughout with a rate-of-rise heat detection system, provided one manual fire
alarm box is installed in a location that is constantly attended by staff during
periods of occupancy by the public.
F-907.2.1.3 Special Assembly Occupancies. In Special Assembly
Occupancies, a shut-off (shunt trip) device shall be provided to automatically
shut off electricity to circuits controlling audio equipment in the facility
upon activation of the fire alarm system or automatic sprinkler
system.
F-907.2.3 Group E. A manual fire alarm system shall be
installed in Group E occupancies. When automatic sprinkler systems or smoke
detectors are installed, such systems or detectors shall be connected to the
building fire alarm
system.
Exceptions:
1. Group E occupancies
with an occupant load of less than 50, where interconnected smoke alarms are
installed in accordance with Section F-907.2.10 and a minimum of one smoke alarm
is installed in each classroom or child care room.
F-907.2.5 Group H. A manual fire alarm system shall be
installed in Group H[-5] occupancies [and in occupancies
used for the manufacture of organic coatings]. An automatic smoke
detection system shall be installed for highly toxic gases, organic peroxides
and oxidizers in accordance with Chapters 37, 39 and 40,
respectively.
F-907.2.6 Group I. A manual fire alarm
system and an automatic fire detection system shall be installed
[in] throughout Group I occupancies except as modified
by Sections F-907.2.6 through F-907.2.6.2.3. An electrically supervised,
automatic smoke detection system shall be provided in waiting areas that are
open to corridors.
F-907.2.9 Group R-2. A manual fire alarm system shall be
installed in Group R-2 occupancies [where:
1. Any
dwelling unit or sleeping unit is located three or more stories above the lowest
level of exit discharge;
2. Any dwelling unit or sleeping unit is
located more than one story below the highest level of exit discharge of exits
serving the dwelling unit or sleeping unit; or
3. The building
contains more than 16 dwelling units or sleeping
units].
Exceptions:
F-907.2.10.1.2 Groups R-2, R-3[,] and R-4 [and
I-1]. Single- or multiple-station smoke alarms shall be installed and
maintained in Groups R-2, R-3[,] and R-4 [and
I-1] regardless of occupant load at all of the following
locations:
[F-907.2.10.1.3 Group I-1. Single- or multiple-station
smoke alarms shall be installed and maintained in sleeping areas in occupancies
in Group I-1. Single- or multiple-station smoke alarms shall not be required
where the building is equipped throughout with an automatic fire detection
system in accordance with Section F-907.2.6.]
F-907.2.10.3 Interconnection. Where more than one smoke
alarm is required to be installed within an individual dwelling unit or sleeping
unit in Group R-2[,] or R-3, [or]
throughout Group R-4, or within an individual dwelling unit
sleeping unit in Group R-1, the smoke alarms shall be interconnected in such a
manner that the activation of one alarm will activate all of the alarms in the
individual unit or throughout the Group R-4 occupancy. The alarm shall be
clearly audible in all bedrooms over background noise levels with all
intervening doors closed.
F-907.2.24 Mixed residential and nonresidential occupancies.
Where a nonresidential occupancy is located below a residential occupancy, an
automatic fire detection system shall be installed throughout the nonresidential
occupancy. Fire alarm notification appliances shall be installed throughout
buildings containing such mixed occupancies and shall be actuated by all
automatic fire detection and manual fire alarm boxes in the
building.
Exceptions:
1. The fire alarm
system and automatic detection is not required where the non-residential
occupancy is equipped throughout with an approved automatic sprinkler system
installed in accordance with Section F-903.3.1.1 and the building has a local
fire alarm that meets the notification requirements of Section
F-907.10.2.
2. Where automatic fire detection is required in
drinking and dining establishments that are below a residential occupancy, heat
detectors are permissible in lieu of smoke detectors in kitchens, in patron
areas designated for smoking, and in patron areas where skillet or sizzling type
entrees such as fajitas are served.
F-907.3 Where required --
retroactive in existing buildings and structures. An approved manual,
automatic or manual and automatic fire alarm system shall be installed in
existing buildings and structures in accordance with Sections F-907.3.1 through
F-907.3.1.[8]12. Where automatic sprinkler protection is
provided in accordance with Section F-903.3.1.1 or F-903.3.1.2 and connected to
the building fire alarm system, automatic heat detection required by this
section shall not be required.
An approved automatic fire detection
system shall be installed in accordance with the provisions of this code and
NFPA 72. Devices, combinations of devices, appliances and equipment shall be
approved. The automatic fire detectors shall be smoke detectors, except an
approved alternative type of detector shall be installed in spaces such as
boiler rooms where, during normal operation, products of combustion are present
in sufficient quantity to actuate a smoke detector.
F-907.3.1 Occupancy requirements. A fire alarm system
shall be installed in accordance with Sections F-907.3.1.1 through
F-907.3.1.[8]12. Existing alarm notification appliances
shall provide a sound level at least 15 decibels (dBA) above the average ambient
sound level in every occupied space within the
building.
Exception: Occupancies with an existing,
previously approved fire alarm system of the same type(s) required by this
section.
F-907.3.1.1 Special Assembly
Occupancies. Existing Special Assembly Occupancies shall comply with
Sections F-907.2.1 and F-907.2.1.3.
F-907.3.1.2 Group
B. A manual fire alarm system shall be installed in existing Group B
occupancies in accordance with Section
F-907.2.2.
F-907.3.1.[1]3 Group E. A
manual fire alarm system shall be installed in existing Group E
occupancies in accordance with Sections
F-907.2.3.
Exceptions:
1. A building with
a maximum area of 1,000 square feet (93 m2) that contains a single
classroom and is located no closer than 50 feet (15,240 mm) from another
building.
2. Group E with an occupant load less than
50, where interconnected smoke alarms are installed in accordance with
Section F-907.2.10 and a minimum of one smoke alarm is installed in each
classroom or child care room.
F-907.3.1.4 Group H. A manual fire
alarm system shall be installed in existing Group H occupancies.
F-907.3.1.[2]5 Group I-1. A manual fire
alarm system and an automatic fire detection system shall be installed
[in] throughout existing Group I-1 residential
care/assisted living
facilities.
Exceptions:
1. Where
each sleeping room has a means of egress door opening directly to an exterior
egress balcony that leads directly to the exits in accordance with Section
F-1013.5, and the building is not more than three stories in
height.
2. In Group I-1 occupancies protected throughout with an
automatic sprinkler system in accordance with Section F-903.3.1.1 or
F-903.3.1.2, automatic fire detection is not required and the exception to
Section F-907.2.6 shall apply.
F-907.3.1.[3]6
Group I-2. A fire alarm system shall be installed in existing Group I-2
occupancies in accordance with Sections
F-907.2.6.
Exceptions:
1. Hospital patient
rooms.
2. Group I-2 occupancies protected throughout with an
automatic sprinkler system in accordance with Section F-903.3.1.1 shall only be
required to have a manual fire alarm system and automatic fire detection in
accordance with Section
F-907.2.6.1.
F-907.3.1.[4]7 Group I-3. A
fire alarm system shall be installed in existing Group I-3 occupancies in
accordance with Sections F-907.2.6.2 through
F-907.2.6.2.3.
F-907.3.1.8 Group I-4. A manual fire
alarm system and an automatic fire detection system shall be installed in
existing Group I-4 occupancies.
F-907.3.1.[5]9
Group R-1 [hotels and motels]. A manual fire alarm system and an
automatic fire detection system shall be installed in interior corridors
and basements in existing Group R-1 occupancies [hotels and
motels more than three stories or with more than 20
guestrooms].
Exception: [Buildings less
than two stories in height where all guestrooms, attics and crawl spaces are
separated by 1-hour fire-resistance-rated construction and each guestroom has
direct access to a public way, exit court or yard.] Automatic fire
detection is not required in buildings equipped throughout with an automatic
sprinkler system in accordance with Sections F-903.3.1.1 or F-903.3.1.2 and
connected to the building fire alarm system.
[F-907.3.1.6
Group R-1 boarding and rooming houses. A fire alarm system shall be
installed in existing Group R-1 boarding and rooming
houses.
Exception: Buildings that have single-station
smoke alarms meeting or exceeding the requirements of Section F-907.2.10.1 and
where the fire alarm system includes at least one manual fire alarm box per
floor arranged to initiate the
alarm.]
F-907.3.1.[7]10 Group R-2. A
manual fire alarm system and an automatic fire detection system
shall be installed in common areas, corridors, and basements in
existing Group R-2 occupancies [more than three stories in height or with
more than 16 dwelling units or sleeping units].
F-907.3.1.[8]11 Group R-4. Multiple-station
smoke alarms [A fire alarm system] shall be installed in
existing Group R-4 residential care/assisted living facilities in accordance
with Section F-907.2.10.
Exception[s]: Smoke
alarms are not required in buildings equipped throughout with an automatic fire
detection system or an automatic sprinkler system installed in accordance with
Section F-903.3.1.1 or F-903.3.1.2.
[1. Where there
are interconnected smoke alarms meeting the requirements of Section F-907.2.10
and there is at least one manual fire alarm box per floor arranged to sound
continuously the smoke alarms.
2. Other manually activated, continuously sounding alarms approved
by the fire code official.]
F-907.3.1.12 Mixed
residential and nonresidential use. Where a nonresidential occupancy is
located below a residential occupancy, an automatic fire detection system shall
be installed throughout the nonresidential occupancy in accordance with Section
F-907.2.24.
F-907.3.2 Single- and multiple-station smoke
alarms. Single- and multiple-station smoke alarms shall be installed and
maintained in existing Group R occupancies in accordance with Sections
F-907.3.2.1 through
F-907.3.2.[3]4.
F-907.3.2.1
General. Existing Group R-1, R-2 and R-3 occupancies not already
provided with single-station smoke alarms shall be provided with approved
single-station smoke alarms. Installation shall be in accordance with Section
F-907.2.10, except as provided in Sections F-907.3.2.2 and F-907.3.2.3. Where
the installation of a smoke alarm in the immediate vicinity of bedrooms will
result in its installation within three feet (914 mm) of a door to a bathroom or
kitchen, installation beyond the immediate vicinity is permitted, but not to
exceed 15 feet (4572 mm) from the bedroom
doors.
Exceptions:
1. Smoke alarms are
not required in sleeping rooms in existing Group R-2 occupancies in high-rise
buildings equipped throughout with an automatic fire extinguishing
system.
2. Smoke alarms are not required in sleeping rooms in
existing Group R-2 orR-3 occupancies in buildings that are not classified as
high-rise buildings.
F-907.3.2.1.1 Verification of smoke
alarms upon sale of building. Upon sale of a building containing a Group R-3
occupancy, the seller shall certify in writing to the buyer that smoke alarms
required by Section F-907.3.2.1 are installed and in proper operating
condition.
F-907.3.2.2 Interconnection. Where more
than one smoke alarm is required to be installed within an individual dwelling
unit or sleeping unit in Group R-2[,] or R-3,
throughout Group [or] R-4, or within an individual sleeping
unit in Group R-1, the smoke alarms shall be interconnected in such a manner
that the activation of one alarm will activate all of the alarms in the
individual unit or throughout the Group R-4 occupancy. The alarm shall be
clearly audible in all bedrooms over background noise levels with all
intervening doors
closed.
Exceptions:
1. Interconnection is
not required in buildings that are not undergoing alterations, repairs or
construction of any kind in Group R-1, R-2 or R-3
occupancies.
2. Smoke alarms in existing areas of Group
R-1, R-2 or R-3 occupancies are not required to be interconnected where
alterations or repairs do not result in the removal of interior wall or ceiling
finishes exposing the structure, unless there is an attic, crawl space or
basement available which could provide access for interconnection without the
removal of interior finishes.
The above exceptions do not apply to
existing Group R-2 occupancies in high-rise buildings where the sound pressure
level of any detector is less than 15 decibels (dBA) above the ambient noise
level in any occupied space within the dwelling unit with intervening doors
closed. For the purposes of this section, the ambient noise level is the
greatest of the following:
1. The noise level resulting from the
operation of all equipment which is intended for use during sleeping hours, such
as heating and/or cooling units, ceiling fans, etc.
2. The noise
level resulting from background noise with windows
open.
3. Thirty-five dBA.
F-907.3.2.3
Power source. In Group R occupancies, single-station smoke alarms shall
receive their primary power from the building wiring provided that such wiring
is served from a commercial source and shall be equipped with a battery backup.
Smoke alarms shall emit a signal when the batteries are low. Wiring shall be
permanent and without a disconnecting switch other than as required for
overcurrent
protection.
Exceptions:
1. In Group R-3
occupancies, [S]smoke alarms are permitted to be solely
battery operated: in existing buildings where no construction is taking place;
in buildings that are not served from a commercial power source; and in existing
areas of buildings undergoing alterations or repairs that do not result in the
removal of interior walls or ceiling finishes exposing the structure, unless
there is an attic, crawl space or basement available which could provide access
for building wiring without the removal of interior
finishes.
2. Electrically powered smoke alarms installed prior to
January 1, 2004 are not required to have a battery backup power
source.
F-907.3.2.4 Testing and maintenance. Tests or
inspections in accordance with the manufacturer’s instructions shall be
conducted at one-week intervals for battery-powered smoke alarms and at
one-month intervals for other than battery-powered smoke
alarms.
F-907.3.2.4.1 Responsibility. Occupants shall
be responsible for the weekly testing and battery replacement of battery-powered
smoke alarms within their dwelling units. Owners shall be responsible for the
repair or replacement of non-operating battery-powered smoke alarms within
dwelling units within three days of written notice.
F-907.4.1 Location. Manual fire alarm boxes shall be
located not more than 5 feet (1524 mm) from the entrance to each exit.
Additional manual fire alarm boxes shall be located so that travel distance to
the nearest box does not exceed 200 feet (60 960
mm).
Exceptions:
1. Manual fire alarm boxes
shall not be required in Group E occupancies where the building is equipped
throughout with an approved automatic sprinkler system, the notification
appliances will activate on sprinkler water flow and manual activation is
provided from a normally occupied location.
2. Buildings of Group
R-2 occupancy with a single exit and not exceeding three stories are not
required to have a manual fire alarm box at each story. One manual fire alarm
box is required in the exit stairway at the exit discharge.
F-907.4.4 Signs (Delete text of subsection and substitute as
follows)
F-907.4.4 Signs. Each manual fire alarm
box shall have a permanent sign mounted immediately adjacent to the box that
reads: "IN CASE OF FIRE -- SOUND ALARM AND CALL 911." It is permissible to
substitute "FIRE DEPARTMENT" for "911."
F-907.9.1 Zoning indicator panel. A zoning indicator panel
and the associated controls shall be provided [in an approved]
at a visible location at the main entrance of the building or other
location approved by the department. The visual zone indication shall lock
in until the system is reset and shall not be cancelled by the operation of an
audible-alarm silencing switch.
F-907.15.1 Existing buildings. Fire alarm systems in existing
Group I and H occupancies and existing high-rise buildings shall be monitored by
an approved supervising station.
Exception: Systems in
high-rise buildings that are monitored on site at a constantly attended
location.
F-907.20.2 Testing. Testing shall be performed in
accordance with Section F-914 and the schedules in Chapter 7 of NFPA 72
or more frequently where required by the fire code official. Where automatic
testing is performed at least weekly by a remotely monitored fire alarm control
unit specifically listed for the application, the manual testing frequency shall
be permitted to be extended to annual.
F-907.20.5 Maintenance, inspection and testing. The
building owner shall be responsible for ensuring that the fire and life safety
systems are maintained in an operable condition at all times. Service personnel
shall meet the qualification requirements of this Chapter and NFPA 72 for
maintaining, inspecting and testing such systems. A written record shall be
maintained and shall be made available to the fire code
official.
Exception: Occupants shall be responsible for the
weekly testing of battery-powered smoke alarms. Owners shall be responsible for
repair or replacement of non-operating smoke alarms within three days of written
notice from the occupant.
F-912.1 Installation. Fire department connections shall be
installed in accordance with this section and the NFPA standard
applicable to the system design.
F-912.1.1 Hose connections.
Fire department connections shall have a minimum of two 2½-inch (64 mm)
internal threaded swivel fittings having National Hose standard threads with
caps.
Exceptions:
1. Manual dry standpipe
systems with 6-inch (152 mm) or larger risers shall have three 2½-inch (64
mm) internal threaded swivel fittings having National Hose standard threads with
caps.
2. Limited area sprinkler systems installed pursuant to
Section F-903.3.5.1.1, in other than basements and stories without openings, are
not required to have a fire department connection.
F-912.2.2 Existing buildings. On existing
buildings, wherever the fire department connection is not visible to approaching
fire apparatus, the fire department connection shall be indicated by an approved
sign of permanent materials mounted on the street front or on the side of
the building. Such sign shall have the [letters "FDC"] words
"SPRINKLER CONNECTION" or "STANDPIPE CONNECTION" at least 6 inches (152 mm)
high and words in letters at least 2 inches (51 mm) high or an arrow to indicate
the location. All such signs shall be subject to the approval of the
[fire code official] Department.
F-912.4 Signs (Delete text of subsection and substitute as
follows)
F-912.4 Signs. A durable, weather
resistant sign shall be mounted at each fire department connection that
indicates the type of system (sprinkler, standpipe or combined sprinkler and
standpipe). Also, where a sprinkler system is not installed throughout a
building, the floor or floors where the sprinklers are installed shall be
indicated on the sign. Where standpipe risers are not interconnected, the sign
shall also indicate in which stairway the standpipe riser that the connection
feeds is located. Wording on signs indicating the type of system shall be a
minimum 1-inch (25 mm) high. Other information shall be a minimum ½-inch
(13 mm) high.
F-912.6 Inspection, testing and maintenance. All fire department
connections shall be periodically inspected, tested and maintained in accordance
with NFPA 25. To ensure there is no debris in the piping, the check valve
shall be removed annually and the piping back-flushed with water to achieve a
full flow through the fire department connection.
F-913.1.1 High-rise buildings. Where electric fire pumps are
newly installed to provide adequate water supplies to fire protection systems in
high-rise buildings, the Philadelphia Building Code requires that such pumps be
connected to a standby power source as provided in NFPA 70. The Philadelphia
Electrical Code prohibits separate (dual) service or connection ahead of service
disconnecting means as a source of power for legally required standby
systems.
F-913.5.5 Lack of suction pressure during the 150 percent
test. Where available suction supplies do not allow flow at 150 percent of
the rated pump capacity during an annual pump test, the fire pump shall be
operated at the maximum allowable discharge. This reduced capacity shall
constitute acceptable test criteria, provided the pump is tested to a minimum of
100 percent of its rated capacity before imposing a 10 psi (69 kPa) suction
pressure on the city water main.