SUBCODE "F" (THE PHILADELPHIA FIRE CODE)
CHAPTER 6 BUILDING SERVICES AND SYSTEMS
F-603.4 Portable unvented heaters. Portable unvented fuel-fired
heating equipment shall be prohibited [in occupancies in Groups A, E, I,
R-1, R-2, R-3 and
R-4].
Exceptions:
1. Listed and approved
unvented fuel-fired heaters in one- and two-family dwellings that are also in
compliance with Section F-308.5.
2. Use of portable unvented
fuel-fired heating equipment is permitted in buildings under
construction.
3. Use of portable unvented fuel-fired heating
equipment is permitted in buildings that are temporarily without
heat.
F-604.4 Operational inspection and testing. Emergency and
standby power systems, including all appurtenant components shall be
inspected and tested under load in accordance with NFPA 110 and NFPA 111.
Tests shall be conducted by a licensed electrical contractor, except that
tests of generator sets shall be accepted from the manufacturer of the generator
or an authorized representative. A copy of the test results shall be sent to the
Department of Licenses and Inspections annually in an approved form. Test
failures shall be reported to the Department of Licenses and Inspections,
repairs shall be made and the system re-tested within 30 days.
F-604.4.1 Transfer switch test. The test of the transfer
switch shall consist of electrically operating the transfer switch from the
normal position to the alternate position and then return to the normal
position. Required standby and emergency systems shall be tested annually for
transfer from primary to standby and/or emergency power under full load
operating conditions. This load shall include all equipment that could be
required to operate at the same time, including fire pumps operating at rated
capacity.
F-604.5 Supervision of maintenance and testing.
Routine maintenance, inspection and operational testing shall be overseen by a
properly instructed individual. A licensed electrical contractor shall
conduct required annual tests, except that tests of generator sets shall be
accepted from the manufacturer of the generator or an authorized
representative.
F-607.2 Emergency signs. An approved pictorial sign of a
standardized design, as indicated in Appendix H, shall be posted adjacent
to each elevator call station on all floors instructing occupants to use the
exit stairways and not to use the elevators in case of fire. The sign shall
read: IN CASE OF FIRE [EMERGENCY], DO NOT USE ELEVATORS.
USE EXIT STAIRS (or USE FIRE EXITS). In high-rise buildings, the
pictorial sign shall be incorporated with an approved floor diagram as indicated
in Appendix H. The emergency sign shall not be required for elevators that
are part of an accessible means of egress complying with Section
F-1007.4.
F-607.3.1 Approved location, number and marking of elevator
keys. Elevator keys for emergency use for door access (shaftway door access)
and override of normal operations (Phase I recall and Phase II firefighter use)
shall be marked as such and readily available at the fire command center or main
lobby desk for use by the fire department and other emergency personnel. In
buildings without a fire command center or main lobby desk, the keys shall be
stored in a break-glass container at the main entrance. There shall be at least
two door access keys and at least six override keys available for emergency
use.