SUBCODE "F" (THE PHILADELPHIA FIRE CODE)
CHAPTER 24 TENTS, CANOPIES AND OTHER MEMBRANE STRUCTURES
F-2404.15 Heating, air conditioning and cooking
equipment. Heating, air conditioning and cooking equipment shall be
in accordance with this section.
F-2404.15.1
Installation. Heating, air conditioning or cooking equipment,
tanks, piping, hoses, fittings, valves, tubing and other related components
shall be installed as specified in the International Mechanical Code and the
International Fuel Gas Code, and shall be approved by the fire code
official.
F-2404.15.3 Location. Cooking and
heating equipment shall not be located within 10 feet (3048 mm) of exits or
combustible materials. Heating and air conditioning units and fuel and power
sources (such as generators) for cooking, heating and air conditioning shall be
located at least 10 feet (3048 mm) from the outside of tents and other membrane
structures, except LP-gas containers shall be located in accordance with Section
F-2404.16. Barricades shall be provided around heating and air conditioning
units, fuel supplies and ducts. Units shall not be in operation during
refueling. While units are in operation, at least one trained person shall
monitor their operation.
F-2404.15.4 Operations. Operations such as
warming of foods, cooking demonstrations and similar operations that use solid
flammables, butane or other similar devices which do not pose an ignition
hazard, [shall be approved] are permitted provided the fuel
containers are spill-proof or placed in chafing dish
holders.
F-2404.15.5 Cooking tents. Tents
where cooking is performed shall not be used for any purpose other than food
preparation and shall be separated from other tents, canopies or membrane
structures by a minimum of 20 feet (6096 mm).