SUBCODE "F" (THE PHILADELPHIA FIRE CODE)
CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION
F-1414.1 Completion before occupancy. In
buildings where an automatic sprinkler system is required by this code or the
International Building Code, it shall be unlawful to occupy any portion of a
building or structure until the automatic sprinkler system installation has been
tested and approved, except as provided in Section [105.3.3]
A-701.5 of the Philadelphia Administrative Code.
SECTION F-1418 ASBESTOS ABATEMENT
F-1418.1
Asbestos Abatement. Asbestos abatement work in buildings shall
be in accordance with the following fire safety
requirements:
1. Materials used in the construction of temporary
enclosures shall be noncombustible or flame resistant in accordance with NFPA
701.
2. Means of egress shall not be blocked, unless an alternate
exiting plan is approved by the fire code official. Exit doors shall not be held
open.
3. Sprinklers, standpipes and other fire suppression
systems shall remain in service, unless otherwise approved by the fire code
official.
4. A sign shall be posted at the building’s fire
alarm annunciator panel indicating the areas undergoing asbestos abatement, as
well as signs at each abatement area.
5. Each abatement area
shall have at least one portable fire extinguisher with a minimum rating of
2-A:10-B:C. All workers shall be instructed in the proper use of the fire
extinguisher.
6. In occupied buildings where automatic fire
detection is taken out of service, a 24-hour fire watch, making hourly rounds
and having a means to contact the Fire Department, shall be
provided.
7. In occupied buildings where negative pressure
ventilation equipment does not exhaust to outdoor areas, a fire watch shall be
provided, as indicated in item 6 above.